P1.24 DC Bus Voltage
Range: 0 to Maximum D.C. Bus Voltage V Default: Read Only
Displays the voltage on the D.C. Bus of the drive.
This voltage must exceed the under-voltage (UV) level for the drive to run.
P1.25 Digital IO Indicators
Range:
0
7
0
6
0
5
0
4
0
3
0
2
0
1
0
0
to 1
7
1
6
1
5
1
4
1
3
1
2
1
1
1
0
Default: Read Only
Displays a set of indicators that represent the status of all the digital inputs and outputs as well as the digital status of the analog inputs.
P1.26 Parameter 1 Saved Value on Error
P1.27 Parameter 2 Saved Value on Error
P1.28 Parameter 3 Saved Value on Error
Range: Dependent on Parameter Saved Default: Read Only
If an error occurs the drive will save the value of the parameter selected by Parameter 1 Save on Error Selector (P4.09), Parameter 2 Save on
Error Selector (P4.10), and Parameter 3 Save on Error Selector (P4.11).
All of these parameters are saved at the point when Error (P1.29) occurs.
P1.29 Error
P1.30 Error History 1
P1.31 Error History 2
P1.32 Error History 3
Range: 0 to 255 Default:
Displays the most recent error (including an active error). Previous errors are listed with Error History 1 being more recent than Error History 3.
Drive Rated Voltage Under Voltage Level Maximum D.C. Bus Voltage
100 V 175 V 415 V
200 V 175 V 415 V
400 V 330 V 830 V
Bit Input/Output Description
Bit 0 T11 Digital IO 1 Set to 1 if the input or output is active
Bit 1 T12 Digital Input 2 Set to 1 if the input is active
Bit 2 T13 Digital Input 3 Set to 1 if the input is active
Bit 3 T14 Digital Input 4 Set to 1 if the input is active
Bit 4 T15 Digital Input 5 Set to 1 if the input is active when T15 Digital Input 5 Type (P6.05) = 0 (Digital Input)
Bit 5 T2 Analog Input 1 Set to 1 if the input is active when T2 Analog Input 1 Type (P6.01) = 1 (Digital)
Bit 6 T4 Analog Input 2 Set to 1 if the input is active when T4 Analog Input 2 Type (P6.02) = 1 (Digital)
Bit 7 T41 Relay Set to 1 if the relay is active