P1.33 Drive Diagnostics
Range: 0 to 15 Default: Read Only
This is a diagnostic parameter that helps identify the next action needed for the drive to run.
Value Name Description
0 Running Drive is running i.e. No Diagnostic information.
1 Inhibited Drive is not enabled. See Sequencer Input and Output Indicators (P1.11)
2 Ready Drive is enabled but has not received a Run signal. See Run and Direction Indicators (P1.12)
3 Locked Inhibit
Drive has stopped and is waiting for the run signal to be removed before it can be made to run again (such as
after an Auto-tune has finished or following a supply loss).
4 Ref 1 Setup
The selected reference is set to None (0). See Frequency Reference 1 to 4 Switch (P2.21).
5 Ref 2 Setup
6 Ref 3 Setup
7 Ref 4 Setup
8 Up/Down Ref The Up/Down Reference has been selected, but not configured. See Up/Down Percent Configuration (P2.14)
9 Freq Ref
The Frequency Reference has been selected, but has not been configured. See T15 Digital Input 5 Type
(P6.05).
10 PID Enable PID Percent has been selected, but the PID has not been enabled. See PID Enable Selector (P5.11)
11 PID Ref
PID Percent has been selected, but the PID Reference has not been configured. See PID Reference Selector
(P5.03)
12 PID Fbk
PID Percent has been selected, but the PID Feedback has not been configured. See PID Feedback
Selector (P5.04)
13 PID Up/Down Ref
PID Percent has been selected and the PID Reference is set to Up/Down, but the Up/Down Reference has not
been configured. See Up/Down Percent Configuration (P2.14).
14 PID Freq Ref
PID Percent has been selected and the PID Reference is set to Frequency input, but the Frequency input has
not been configured. See T15 Digital Input 5 Type (P6.05).
15 PID Freq Fbk
PID Percent has been selected and the PID feedback is set to Frequency input, but the Frequency input has not
been configured, see T15 Digital Input 5 Type (P6.05).
16 Current Loop Loss
Drive has stopped because the current loop has been lost on one of the analog inputs, see Alarm Indicators
(P1.09).
17 Drive State
The drive is not running because it is currently in Supply Loss, Injecting D.C., Error, Under Voltage or it is still
initialising, see Drive State (P1.05).