Safety information Product information Mechanical installation Electrical installation Multi axis system design Technical data
Digitax HD M75X Series Installation and Technical Guide 103
Issue Number: 5
Table 6-8 Open loop and RFC-A maximum permissible continuous output current @ 50 °C (122 °F) ambient (cooling fan at middle speed)
6.1.3 Continuous rating
Table 6-9 Continuous rating with no overload @ 0 Hz output frequency, 40 °C (104 °F) ambient
Model
Heavy Duty
Maximum permissible continuous output current (A) (Pr 06.045 = 7 or -7)
2 kHz 3 kHz 4 kHz 6 kHz 8 kHz 12 kHz 16 kHz
200 V
01200022 2.2 2.2 2.2 2.2 2.2 2.2 2.2
01200040 4.0 4.0 4.0 4.0 4.0 4.0 4.0
01200065 6.5 6.5 6.5 6.5 6.2 5.5 4.7
02200090 8.9 8.6 8.4 8.0 7.8 7.6 7.6
02200120 8.9 8.6 8.4 8.0 7.8 7.6 7.6
03200160 16.0 15.8 15.2 13.8 12.6 11.6 10.4
400 V
01400015 1.5 1.5 1.5 1.5 1.5 1.5 1.5
01400030 3.0 3.0 2.9 2.7 2.5 2.3 1.8
01400042 3.2 3.1 2.9 2.7 2.5 2.3 1.8
02400060 6.0 6.0 6.0 6.0 6.0 5.5 4.8
02400080 8.0 7.7 7.2 6.7 6.2 5.5 4.8
02400105 8.1 7.7 7.2 6.7 6.2 5.5 4.8
03400135 13.5 13.3 12.6 10.9 9.6 7.5 6.1
03400160 13.8 13.3 12.6 10.9 9.6 7.5 6.1
Model
Heavy Duty
Nominal rating Maximum permissible continuous output current (A) at 0 Hz with no overload
kW hp 2 kHz 3 kHz 4 kHz 6 kHz 8 kHz 12 kHz 16 kHz
200 V
01200022 0.37 0.5 2.2 2.2 2.2
01200040 0.75 1.0 4.0 4.0 4.0
01200065 1.1 1.5 6.5 6.5 6.5
02200090 2.2 2.0 9.0 9.0 9.0
02200120 2.2 3.0 12.0 11.6 10.8
03200160 4.0 5.0 16.0 16.0 16.0
400 V
01400015 0.37 0.75 1.5 1.5 1.5
01400030 0.75 1.5 3.0 3.0 3.0
01400042 1.5 2.0 4.2 4.2 4.2
02400060 2.2 3.0 6.0 6.0 6.0
02400080 3.0 5.0 8.0 8.0 6.9
02400105 4.0 5.0 10.5 9.4 6.9
03400135 5.5 7.5 13.5 11.5 9.3
03400160 5.5 10.0 16.0 15.8 13.8 11.5 9.3