62 Digitax HD M75X Series Installation and Technical Guide
Issue Number: 5
Table 4-15 External EMC filter ratings
For external EMC filter dimensions and terminal data refer to section 3.14 External EMC filter on page 36.
The installer of the drive is responsible for ensuring compliance with the EMC regulations that apply in the country in which the drive is to be used.
4.10.2 Grounding hardware
The drive is supplied with a cable screen bracket to facilitate EMC compliance. The bracket provides a convenient method for direct grounding of
cable shields without the use of “pig-tails”. Cable shields can be bared and clamped to the cable screen bracket using metal clips or cable ties. Note
that, where applicable, the shield must in all cases be continued through the cable screen bracket to the intended terminal on the drive, in accordance
with the connection details for the specific signal.
• See Figure 4-10 for details on installing the cable screen bracket.
Figure 4-9 Attaching the cable screen bracket to the motor, feedback and control wiring (frame sizes 1 and 2)
• Expose outer cable shields (1).
• The cable screen bracket (2) must be tie wrapped to the motor, feedback and control wiring (3).
Part number
Number of
phases
Maximum continuous
current
Maximum voltage
rating
Power
losses at
rated
current
IP
rating
Weight
Operational
leakage current
Worst
case
leakage
current
@40C
(104F)
@50C
(122F)
IEC UL
AAVVW kglb mA mA
4200-3503 1 30 27.3 250 250 6.1 20 0.7 1.5 5.4 10.8
4200-5033 1 55 50.1 250 250 9.9 20 1.2 2.6 11 22
4200-6034 1 65.7 60 250 250 5.5 20 1.8 4.0 3.4 6.8
4200-8744 3 7.7 7 480 480 3.8 20 0.5 1.1 33 178.2
4200-6002 3 11 10 480 480 10 20 1.2 2.64 16 90
4200-6001 3 17 15.5 250 250 13 20 1.2 2.64 8 50
4200-1644 3 17.5 16 480 480 6.1 20 0.8 1.76 33 178.2
4200-5833 3 32.9 30 480 480 11.8 20 1.2 2.64 33 178.2
4200-3233 3 46 42 480 480 15.7 20 1.4 3.1 33 178.2
4200-5534 3 60.2 55 480 480 25.9 20 2.0 4.4 33 178.2
4200-7534 3 82.2 75 480 480 32.2 20 2.7 6.0 33 178.2
4200-0035 3 109.5 100 480 480 34.5 20 4.3 9.5 33 178.2
High ground leakage current
When an EMC filter is used, a permanent fixed ground connection must be provided which does not pass through a connector or flexible
power cord. This includes the internal EMC filter.