SK 54xE – Users Manual for Frequency Inverters
154 BU 0505 EN-3021
P560
Parameter, Saving mode
(Saving mode parameter)
S
0 ... 2
{ 1 }
0 = Only in RAM, changes to the parameter settings are no longer saved on the EEPROM.
All previously saved settings are retained, even if the FI is disconnected from the mains.
1 = RAM and EEPROM, all parameter changes are automatically written to the EEPROM
and remain stored there even if the FI is disconnected from the mains supply.
2 = OFF, no saving in RAM and EEPROM possible (no parameter changes are accepted)
NOTE:
If BUS communication is used to implement parameter changes, it must be ensured
that the maximum number of write cycles (100,000 x) in the EEPROM is not
exceeded.
Pos: 375 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ P6xx Positionierun g [SK 5xxE] @ 0\mod_13281702198 88_388.docx @ 12270 @ 5 @ 1
Positioning
The parameter group P6xx is used to set the POSICON positioning control and is included above the
version SK 530E.
A detailed description of these parameters can be found in manual BU 0510. (www.nord.com)
Pos: 376 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ P7xx Informationen @ 0\ mod_1328170311705_388. docx @ 12293 @ 5 @ 1
Information
Parameter Setting value / Description / Note Supervisor Parameter set
Pos: 377 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P700- P799/Parameter P700 – Akt ueller Betriebszust and @ 0\mod_132817048381 0_388.docx @ 12318 @ @ 1
P700 [-01]
...
[-03]
Actual operating status
(Actual operating status)
0.0 ... 25.4
Display of current messages for the present operating status of the frequency inverter such as
faults, warnings or the reason why switch-on is disabled (please see chapter 6 "Operating status
messages").
[-01] = Present fault, shows the currently active (unacknowledged) fault (please see section
"Error messages").
[-02] = Present warning, indicates a current warning message (please see section "Warning
messages").
[-03] = Reason for disabled starting, indicates the reason for an active start disable (please see
section "Switch-on block messages").
NOTE
SimpleBox / ControlBox: the error numbers of the warning messages and faults can be displayed
using SimpleBox and ControlBox.
ParameterBox: with the ParameterBox the messages are displayed in plain text.. In addition, the
reason for a possible disabling of starting can also be displayed.
Bus: The display of bus-
level error messages is displayed in decimal integer format. The
displayed value must be divided by 10 in order to correspond with the correct format.
Example: Display: 20 → Error number: 2.0
Pos: 378 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P700- P799/Parameter P701 – Letzt e Störung 1...5 @ 0\mod_13281 70536746_388.doc x @ 12341 @ @ 1
P701 [-01]
...
[-05]
Last fault 1 ... 5
(Last fault 1...5)
0.0 ... 25.4 This parameter stores the last 5 faults (please see section "Error messages").
The SimpleBox / ControlBox must be used to select the corresponding memory location 1...5-
(Array parameter), and confirmed using the OK / ENTER key to read the stored error code.