SK 54xEUsers Manual for Frequency Inverters
160 BU 0505 EN-3021
P738
Usage rate motor
(Actual utilisation of motor)
0 ... 1000 % Shows the actual motor load. Basis for calculation is the motor data P203. The actually recorded
current is related to the nominal motor current.
Pos: 419 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P700- P799/Parameter P739 Akt uelle Temperatur Küh lkörper [SK 54xE] @ 0\mod_1328 175157199_388.doc x @ 13284 @ @ 1
P739 [-01]
...
[-03]
Heatsink temperature
(Actual heat sink temperature)
0 ... 150 °C Displays the actual FI temperature.
[-01] = Heat sink temperature: Displays the actual FI heat sink temperature. This value is used
for overtemperature switch-off (E001), error message 1.0.
[-02] = Internal temperature: shows the actual internal temperature of the inverter. This value is
used for overtemperature switch-off (E001), error message 1.1.
[-03] = Motor temperature KTY temperature: shows the actual motor temperature when
monitoring with a KTY temperature sensor.
Pos: 421 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P700- P799/Parameter P740 Pr ozessdaten Bus In [SK 54xE] @ 0\mod _1328177837899_388.doc x @ 13336 @ @ 1
P740 [-01]
...
[-23]
Process Data Bus In
(Process data Bus In)
S
0000 ... FFFF (hex)
This parameter informs
about the actual control
word and the setpoints that
are transferred via the bus
systems.
For display, a BUS system
must be selected in P509.
Standardisation: 8.7
"
Standardisation of setpoint
/ target values"
[-01 ] = Control word
Control word, source from
P509.
[-02] = set value 1 (P510/1)
[-03] = set value 2 (P510/1)
[-04] = set value 3 (P510/1)
[-05] = set value 4 (P510/1)
[-06] = set value 5 (P510/1)
Setpoint data from main
setpoint (P510 [-01]).
[-07] = res. Stat InBit P480
The displayed value depicts all
Bus In Bit sources linked with
"OR".
[-08] = Parameter data In 1
[-09] = Parameter data In 2
[-10] = Parameter data In 3
[-11] = Parameter data In 4
[-12] = Parameter data In 5
Data during parameter transfer:
Order label (AK),Parameter
number (PNU), Index (IND),
Parameter value (PWE 1/2)
[-13] = set value 1 (P510/2)
[-14] = set value 2 (P510/2)
[-15] = set value 3 (P510/2)
[-16] = set value 4 (P510/2)
[-17] = set value 5 (P510/2)
Setpoint data from the master
function value (Broadcast), if
P509 = 9/10
(P510 [-02])
[-18] = Control word PLC
Control word, source PLC
[-19] = set value 1 PLC
[-20] = set value 2 PLC
[-21] = set value 3 PLC
[-22] = set value 4 PLC
[-23] = set value 5 PLC
Setpoint data from the PLC.