23
– Timer controlled with different humidity setpoints:
Select “Hum.Setpoint” in the control settings menu, then press the <Set> key.
Select “Timer”, then press the <Set> key. In the upcoming modication dialogue activate the timer
function and conrm the setting with the <Set> key.
If the timer is activated, up to eight switching points (events 1 - 8) with different humidity setpoints
can be dened. Each switching point is dened by a weekday or weekday range, the switching
point and the humidity setpoint.
Conguration notes:
– the settings of an event remain active up to the next event.
– the software does not check the plausibility of the timer settings. Therefore, make sure your
settings make sense.
– the On/Off timer (see chapter 4.6.5) overrides the humidity setpoint timer.
4.6.3.6 Setting the proportional range for the internal P/PI controller
Note: This menu item is available only if the internal P or PI controller is activated.
Select “P-Band” in the control settings menu, then press the <Set> key.
In the upcoming modication dialogue set the proportional range in % for the internal P/PI controller.
Factory setting: 18 %
Options: 6...65 %
P-Band
18 %rH
18 %rH
Esc Set
Controls
Hum.Setpoint:Set
P-Band :18%rH
Integr.-Time:8min
Controlsign.:0-10V
Lim. Control:O
Esc Set
Settings
Controls :Set
Power Limit :100%
On/O Timer :Set
Language :English
GFCI-Mode :On
Esc Set
Hum.Setpoint
Hum.Setpoint:50%rH
Timer :O
Esc Set
Timer
O
On
On
Esc Set
Hum.Setpoint
Event 1 :06:00
Event 2 :18:00
Event 3 :--:--
Timer :On
Event 4 :--:--
Esc Set
Event 2
Time :18:00
Hum.Setpoint:50%rH
Weekday :Mo-Fr
Esc Set
Hum.Setpoint
Event 1 :06:00
Event 2 :18:00
Event 3 :--:--
Timer :On
Event 4 :--:--
Esc Set
Weekday
O
Mo-Fr
Mo-Sa
Mo-Fr
Mo-So
Esc Set
Event 2
Time :18:00
Hum.Setpoint:50%rH
Weekday :Mo-Fr
Esc Set
Event 2
Time :18:00
Hum.Setpoint:50%rH
Weekday :Mo-Fr
Esc Set
Hum.Setpoint
50%rH
50%rH
Esc Set
Time
18:00
18:00
Esc Set
Settings
Controls :Set
Power Limit :Set
On/O Timer :Set
Language :English
GFCI-Mode :On
Esc Set
Controls
Controlsign.:0-10V
Hum.Setpoint:Set
P-Band :18%rH
Hum.Control :Int.(PI)
Integr.-Time:8min
Esc Set