CP Strobe Warning Lamp
45 OMICRON
Figure 19: CP Strobe Warning Lamp connected to the main device (here CIBANO 500) with the CP Strobe connection cable
7.4 Testing
To test the CP Strobe Warning Lamp:
1. Disconnect all test leads and cables – except the CP Strobe connection cable – from the main
device. Do not connect any cables during the test of the CP Strobe Warning Lamp.
2. Release the Emergency Stop button on the front panel of the main device.
3. Create an arbitrary manual test as described in the User Manual of the main device.
NOTE! See one or more of the following manuals:
• CIBANO 500 User Manual
• CPC PTM User Manual
• TESTRANO 600 User Manual
4. Execute the created test by clicking Start in the Primary Test Manager workspace and pressing the
Measurement Start/Stop button on the front panel of the main device.
5. Now, the CP Strobe Warning Lamp should flash while the test is running.
6. Press the main device’s Measurement Start/Stop button.
7. Press the main device’s Emergency Stop button.
CP Strobe Warning Light
CP Strobe connection cable