EasyManuals Logo

Omron 3G3M1-A4004-ECT User Manual

Omron 3G3M1-A4004-ECT
850 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #215 background imageLoading...
Page #215 background image
6-3
Motor Parameter Settings
6-3-1
Induction Motor Basic Settings
When running an induction motor, set the following parameters to match the rated value of the motor
used and the design values of the machinery.
Parameter No. Function name Data
Default da-
ta
Unit
3004Hex-05Hex/
3009Hex-03Hex
1st Base Frequency/2nd Base
Frequency
*1
5.0 to 590.0
50.0 Hz
3004Hex-06Hex/
3009Hex-04Hex
1st Rated Voltage at Base Fre-
quency/2nd Rated V
oltage at
Base Frequency
*1
80 to 240: (200 V class series)
160 to 500: (400 V class series)
Dependent
on capacity
V
3004Hex-04Hex/
3009Hex-02Hex
1st Maximum Output
Frequency/2nd Maximum Output
Frequency
*1
5.0 to 590.0
60.0
Hz
*1. To enable switching to the 1st and 2nd control, allocate “12: SET (2nd control)” to either of input terminal
[DI1] to [DI7].
6-3-2
Base Frequency and Maximum Frequency of Motor
To configure the V/f control characteristics output to the motor, set the base frequency and maximum
frequency of your motor.
For the base frequency
, set the rated frequency of the motor (the frequency listed on the motor rating
nameplate).
For the maximum frequency, set the highest frequency required for your application. However, do not
exceed the maximum rotation speed of the motor.
Then, set the motor rated voltage to 1st Rated Voltage at Maximum Output Frequency
(3004Hex-07Hex)/2nd Rated Voltage at Maximum Output Frequency (3009Hex-05Hex).
Parameter No. Function name Data
Default da-
ta
Unit
3004Hex-05Hex/
3009Hex-03Hex
1st Base Frequency/2nd Base
Frequency
*1
5.0 to 590.0
50.0 Hz
3004Hex-04Hex/
3009Hex-02Hex
1st Maximum Output
Frequency/2nd Maximum Output
Frequency
*1
5.0 to 590.0
60.0 Hz
3004Hex-06Hex/
3009Hex-04Hex
1st Rated Voltage at Base Fre-
quency/2nd Rated V
oltage at
Base Frequency
*1
80 to 240: (200 V class series)
160 to 500: (400 V class series)
Dependent
on capacity
V
3004Hex-07Hex/
3009Hex-05Hex
1st Rated V
oltage at Maximum
Output Frequency/2nd Rated
Voltage at Maximum Output Fre-
quency
*1
80 to 240: (200 V class series)
160 to 500: (400 V class series)
Dependent
on capacity
V
*1. To enable switching to the 1st and 2nd control, allocate “12: SET (2nd control)” to either of input terminal
[DI1] to [DI7].
6 Basic Settings
6-17
M1 Series EtherCAT Type User’s Manual (I670)
6-3 Motor Parameter Settings
6
6-3-1 Induction Motor Basic Settings

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron 3G3M1-A4004-ECT and is the answer not in the manual?

Omron 3G3M1-A4004-ECT Specifications

General IconGeneral
BrandOmron
Model3G3M1-A4004-ECT
CategoryInverter
LanguageEnglish

Related product manuals