Basic Parameter Settings
Item Inverter parameter Setting range
De-
scrip-
tion
Default
value
Ca-
pacity
3007Hex-0
3Hex/
3009Hex-1
1Hex
1st Motor Capacity/2nd
Motor Capacity
0.01 to 1000 kW
Sets
the
motor
capaci-
ty.
Dependent
on capacity
Num-
ber of
poles
3007Hex-0
2Hex/
3009Hex-1
0Hex
1st Motor Pole
Number/2nd Motor Pole
Number
2 to 128 poles
Sets
the
num-
ber of
poles
of the
motor.
4
Fre-
quency
3004Hex-0
5Hex/
3009Hex-0
3Hex
1st Base Frequency/2nd
Base Frequency
5.0 to 590.0 Hz
Sets
the
base
fre-
quency
of the
motor.
50.0
3004Hex-0
4Hex/
3009Hex-0
2Hex
1st Maximum Output Fre-
quency/2nd Maximum
Output Frequency
5.0 to 590.0 Hz
Sets
the
maxi-
mum
fre-
quency
of the
motor.
60.0
V
olt-
age 3004Hex-0
6Hex/
3009Hex-0
4Hex
1st Rated Voltage at Base
Frequency/2nd Rated
Voltage at Base Frequen-
cy
80 to 240 V
: AVR operation (200 V
class series)
160 to 500 V: AVR operation (400 V
class series)
Sets
the
base
voltage
of the
motor.
Dependent
on capacity
3004Hex-0
7Hex/
3009Hex-0
5Hex
1st Rated Voltage at Max-
imum Output
Frequency/2nd Rated
Voltage at Maximum Out-
put Frequency
80 to 240 V
: AVR operation (200 V
class series)
160 to 500 V: AVR operation (400 V
class series)
Sets
the
maxi-
mum
voltage
of the
motor.
Dependent
on capacity
Cur-
rent
3007Hex-0
4Hex/
3009Hex-1
2Hex
1st Motor Rated
Current/2nd Motor Rated
Current
0.00 to 500.0 A
Set the
rated
current
of the
motor.
Dependent
on capacity
7 Vector Control and Applied Functions
7-5
M1 Series EtherCAT Type User’s Manual (I670)
7-1 Details of Motor Control Methods
7
7-1-2 Basic Motor Parameter Settings

Table of Contents

Related product manuals