When this terminal is reset, the torque limit setting is disabled and the inverter uses the maximum
value (300%) as the torque limit value.
When the torque limit enabled (TL) function is not allocated to a multifunction input terminal, the tor-
que limit function is enabled at all times.
• The torque limit function regards the motor rated torque as 100%.
•
When “132: TRQ (Torque limited)” is set to Output Terminal [DO1] Function Selection
(3005Hex-15Hex) or Output Terminal [ROA, ROB] Function Selection (3005Hex-1CHex), the torque
limit function can be checked to see if it is activated by the status of the torque limited signal.
• To enable the torque limit value by analog voltage, set “7: Analog torque limiter” to Input Terminal
[AI1] Function Selection (3005Hex-3EHex). Analog inputs 0 to 10 V are equivalent to torque limit
values 0% to 300%. The torque limit value set by analog input is enabled in all operation modes.
Parameter No. Function name Data Default data Unit
3004Hex-29Hex
Torque Limit 1 (power run-
ning)
0 to 300 (In four quadrants,
forward driving)
300 %
3004Hex-2AHex
Torque Limit 2 (regenera-
tion)
0 to 300 (In four quadrants,
reverse regeneration)
3005Hex-11Hex
Torque Limit 3 (power run-
ning)
0 to 300 (In four quadrants,
reverse driving)
3005Hex-12Hex
Torque Limit 4 (regenera-
tion)
0 to 300 (In four quadrants,
forward regeneration)
3005Hex-02Hex to
3005Hex-06Hex,
3005Hex-63Hex,
3005Hex-64Hex
Input Terminal [DI1] to [DI7]
Function Selection
14: TRQ1 (Torque limit
switching 1)
- -
184: TL (Torque control en-
abled)
185: TRQ2 (Torque limit
switching 2)
3005Hex-15Hex
Output Terminal [DO1]
Function Selection
132: TRQ (Torque limited) - -
3005Hex-1CHex
Output Terminal [ROA,
ROB] Function Selection
3005Hex-3EHex
Input Terminal [AI1] Func-
tion Selection
7: Analog torque limiter - -
3008Hex-4BHex
Torque Limit Function Se-
lection
0: Torque limit
1: T
orque current limit
1 -
3008Hex-4CHex
T
orque Limit Operation Se-
lection
0: Four quadrants inde-
pendent
0 -
1: Four quadrants identical
3008Hex-4DHex
Frequency Rising Limit for
T
orque Limit
0.0 to 590.0 5.0
Hz
Details of Four Quadrant Independent (3008Hex-4CHex = 0)
The torque limit (3004Hex-29Hex, 3004Hex-2AHex, 3005Hex-11Hex, 3005Hex-12Hex) when “0:
Four quadrant independent” is selected at Torque Limit Operation Selection (3008Hex-4CHex) is
as shown in the figure below
.
7 Vector Control and Applied Functions
7-83
M1 Series EtherCAT Type User’s Manual (I670)
7-11 Torque limit function
7
7-11-1 Torque Limit Function Settings