Parameter No. Item Range Display item
301AHex-32Hex
Fourth Last Alarm Info.
Running Status
0000Hex to
FFFFHex
The operation status is displayed by a
four-digit hexadecimal.
301AHex-2CHex
Fourth Last Alarm Info. Cu-
mulative Ope. time
0 to 655,350 hours
The number of operations of the motor
(number of times the RUN command for
the inverter is turned ON) is calculated
and displayed.
301AHex-2DHex
Fourth Last Alarm Info.
Main Circuit DC V
oltage
0.0 to 999.0 [V]
The Main Circuit DC V
oltage of the in-
verter is displayed.
301AHex-31Hex
Fourth Last Alarm Info. Cu-
mulative Running Time
0 to 655,350 hours
The cumulative time of the inverter
RUN state is displayed.
6 Fifth last alarm
301AHex-34Hex
Fifth Last Alarm Info. Out-
put Frequency
0.00 to 99.99,
100.0 to 590.0
[Hz]
The output frequency before slip com-
pensation is displayed in increments of
0.01 Hz. A value of 100.0 Hz or higher
is displayed in increments of 0.1 Hz.
301AHex-35Hex
Fifth Last Alarm Info. Out-
put Current
0.00 to 99.99,
100.0 to 655.3 [A]
The output current is displayed. A cur-
rent value of 100.0A or higher is dis-
played in increments of 0.1 A.
Display unit: A (Ampere)
301AHex-3CHex
Fifth Last Alarm Info. Run-
ning Status
0000Hex to
FFFFHex
The operation status is displayed by a
four-digit hexadecimal.
301AHex-36Hex
Fifth Last Alarm Info. Cu-
mulative Ope. T
ime
0 to 655,350 hours
The number of operations of the motor
(number of times the RUN command for
the inverter is turned ON) is calculated
and displayed.
301AHex-37Hex
Fifth last Alarm Info. Main
Circuit DC Voltage
0.0 to 999.0 [V]
The Main Circuit DC V
oltage of the in-
verter is displayed.
301AHex-3BHex
Fifth last Alarm Info. Cu-
mulative Running time
0 to 655,350 hours
The cumulative time of the inverter
RUN state is displayed.
Running Status 3 Monitor [3003Hex-47Hex]
The operation status 3 displays the status allocated to each bit by a four-digit hexadecimal.
The allocation for 0 to 15 bits of the operation status is described in the table below.
Bit Symbol Description
15 - Fixed to 0
14 ID2 Current detection 2
13 IDL Low current detection
12 ID Current detection
11 OLP Overload prevention controlling
10 LIFE Lifetime alarm
9 OH Heat sink overheat early warning
8 TRY During retry
7 FAN Fan operation signal
6 KP During touch panel operation
5 OL Motor overload early warning
4 IPF During restart after instantaneous power failure
3 SWM2 Motor 2 selection
8 Other Functions
8-21
M1 Series EtherCAT Type User’s Manual (I670)
8-1 Status Monitors
8
8-1-4 Alarm information