When this terminal is reset, the torque limit setting is disabled and the inverter uses the maximum
value (300%) as the torque limit value.
When the torque limit enabled (TL) function is not allocated to a multifunction input terminal, the tor-
que limit function is enabled at all times.
The torque limit function regards the motor rated torque as 100%.
When “132: TRQ (Torque limited)” is set to Output Terminal [DO1] Function Selection
(3005Hex-15Hex) or Output Terminal [ROA, ROB] Function Selection (3005Hex-1CHex), the torque
limit function can be checked to see if it is activated by the status of the torque limited signal.
To enable the torque limit value by analog voltage, set “7: Analog torque limiter” to Input Terminal
[AI1] Function Selection (3005Hex-3EHex). Analog inputs 0 to 10 V are equivalent to torque limit
values 0% to 300%. The torque limit value set by analog input is enabled in all operation modes.
Parameter No. Function name Data Default data Unit
3004Hex-29Hex
Torque Limit 1 (power run-
ning)
0 to 300 (In four quadrants,
forward driving)
300 %
3004Hex-2AHex
Torque Limit 2 (regenera-
tion)
0 to 300 (In four quadrants,
reverse regeneration)
3005Hex-11Hex
Torque Limit 3 (power run-
ning)
0 to 300 (In four quadrants,
reverse driving)
3005Hex-12Hex
Torque Limit 4 (regenera-
tion)
0 to 300 (In four quadrants,
forward regeneration)
3005Hex-02Hex to
3005Hex-06Hex,
3005Hex-63Hex,
3005Hex-64Hex
Input Terminal [DI1] to [DI7]
Function Selection
14: TRQ1 (Torque limit
switching 1)
- -
184: TL (Torque control en-
abled)
185: TRQ2 (Torque limit
switching 2)
3005Hex-15Hex
Output Terminal [DO1]
Function Selection
132: TRQ (Torque limited) - -
3005Hex-1CHex
Output Terminal [ROA,
ROB] Function Selection
3005Hex-3EHex
Input Terminal [AI1] Func-
tion Selection
7: Analog torque limiter - -
3008Hex-4BHex
Torque Limit Function Se-
lection
0: Torque limit
1: T
orque current limit
1 -
3008Hex-4CHex
T
orque Limit Operation Se-
lection
0: Four quadrants inde-
pendent
0 -
1: Four quadrants identical
3008Hex-4DHex
Frequency Rising Limit for
T
orque Limit
0.0 to 590.0 5.0
Hz
Details of Four Quadrant Independent (3008Hex-4CHex = 0)
The torque limit (3004Hex-29Hex, 3004Hex-2AHex, 3005Hex-11Hex, 3005Hex-12Hex) when “0:
Four quadrant independent” is selected at Torque Limit Operation Selection (3008Hex-4CHex) is
as shown in the figure below
.
7 Vector Control and Applied Functions
7-83
M1 Series EtherCAT Type User’s Manual (I670)
7-11 Torque limit function
7
7-11-1 Torque Limit Function Settings