This function is exclusively for the 1st control. The maintenance timer signal is not output even if 2nd
Cumulative Motor Run Time (3009Hex-34Hex)/2nd Startup Counter for Motor (3009Hex-35Hex)
exceeds the set time period or set number of times.
<For half-yearly maintenance> <For maintenance performed every 1,000 times>
1st Cumulative Motor Run Time (3008Hex-5FHex)
Time
3008Hex-4FHex = 876
(8,760 hours = 1 year)
3008Hex-4FHex = 438
(4,380 hours = 6 months)
Maintenance timer
“MNT”
ON
ON
3008Hex-5FHex
3008Hex-4FHex
Time
1st Startup Count for Motor (3008Hex-2DHex)
3008Hex-50Hex = 07D0
(2,000 times)
3008Hex-50Hex = 03E8
(1,000 times)
Maintenance timer
“MNT”
ON
ON
3008Hex-2DHex
3008Hex-50Hex
When the maintenance time is reached, or when the set number of startups for maintenance is
reached, again set a numeric value to 1st Motor Maintenance Interval (3008Hex-4FHex) or 1st Preset
Startup Count for Motor Maintenance (3008Hex-50Hex) to reset the output signal, and restart the
measurement of the time period or the number of startups.
8-8-9
Logic Operation Output Signal (LOG1 to LOG3)
Logical operations (AND, OR, XOR) are performed on signals that can be allocated to output terminals
[DO1] and [ROA, ROB], and the result can be output from output terminals. Set “206: LOG1 (Logic
operation output 1),” “207: LOG2 (Logic operation output 2),” or “208: LOG3 (Logic operation output
3)” to Output Terminal [DO1] Function Selection (3005Hex-15Hex) and Output T
erminal [ROA, ROB]
Function Selection (3005Hex-1CHex). However, “206: LOG1 (Logic operation output 1)” to “208:
LOG3 (Logic operation output 3)” cannot be selected for the operation target data.
Logic output
signal selection 1
Logic output
signal selection 2
LOGx (AND)
LOGx (OR)
LOGx (XOR)
8 Other Functions
8-83
M1 Series EtherCAT Type User’s Manual (I670)
8-8 Functions Related to Protection, Warning and Various Output Signals
8
8-8-9 Logic Operation Output Signal (LOG1 to LOG3)

Table of Contents