Parameter No. Item Range Display item
3011Hex-45Hex
Last Alarm Info. Main Cir-
cuit DC Voltage
0.0 to 999.0 [V]
The Main Circuit DC V
oltage of the in-
verter is displayed.
301AHex-13Hex
Last Alarm Info. Cumula-
tive Running Time
0 to 655,350 hours
The cumulative time of the inverter
RUN state is displayed.
3 Second last alarm
3012Hex-01Hex
Second Last Alarm Info.
Output Frequency
0.00 to 99.99,
100.0 to 590.0
[Hz]
The output frequency before slip com-
pensation is displayed in increments of
0.01 Hz. A value of 100.0 Hz or higher
is displayed in increments of 0.1 Hz.
3012Hex-02Hex
Second Last Alarm Info.
Output Current
0.00 to 99.99,
100.0 to 655.3 [A]
The output current is displayed. A cur-
rent value of 100.0A or higher is dis-
played in increments of 0.1 A.
Display unit: A (Ampere)
3012Hex-06Hex
Second Last Alarm Info.
Running Status
0000Hex to
FFFFHex
The operation status is displayed by a
four-digit hexadecimal.
3012Hex-07Hex
Second Last Alarm Info.
Cumulative Ope. T
ime
0 to 655,350 hours
The number of operations of the motor
(number of times the RUN command for
the inverter is turned ON) is calculated
and displayed.
3012Hex-09Hex
Second Last Alarm Info.
Main Circuit DC Voltage
0.0 to 999.0 [V]
The Main Circuit DC V
oltage of the in-
verter is displayed.
301AHex-1DHex
Second last Alarm Info.
Cumulative Running Time
0 to 655,350 hours
The cumulative time of the inverter
RUN state is displayed.
4 Third last alarm
3012Hex-33Hex
Third Last Alarm Info. Out-
put Frequency
0.00 to 99.99,
100.0 to 590.0
[Hz]
The output frequency before slip com-
pensation is displayed in increments of
0.01 Hz. A value of 100.0 Hz or higher
is displayed in increments of 0.1 Hz.
3012Hex-34Hex
Third Last Alarm Info. Out-
put Current
0.00 to 99.99,
100.0 to 655.3 [A]
The output current is displayed. A cur-
rent value of 100.0A or higher is dis-
played in increments of 0.1 A.
Display unit: A (Ampere)
3012Hex-38Hex
Third Last Alarm Info. Run-
ning Status
0000Hex to
FFFFHex
The operation status is displayed by a
four-digit hexadecimal.
3012Hex-39Hex
Third Last Alarm Info. Cu-
mulative Ope. T
ime
0 to 655,350 hours
The number of operations of the motor
(number of times the RUN command for
the inverter is turned ON) is calculated
and displayed.
3012Hex-3BHex
Third Last Alarm Info. Main
Circuit DC Voltage
0.0 to 999.0 [V]
The Main Circuit DC V
oltage of the in-
verter is displayed.
301AHex-27Hex
Third last Alarm Info. Cu-
mulative Running Time
0 to 655,350 hours
The cumulative time of the inverter
RUN state is displayed.
5 Fourth last alarm
301AHex-2AHex
Fourth last Alarm Info. Out-
put Frequency
0.00 to 99.99,
100.0 to 590.0
[Hz]
The output frequency before slip com-
pensation is displayed in increments of
0.01 Hz. A value of 100.0 Hz or higher
is displayed in increments of 0.1 Hz.
301AHex-2BHex
Fourth last Alarm Info. Out-
put Current
0.00 to 99.99,
100.0 to 655.3 [A]
The output current is displayed. A cur-
rent value of 100.0A or higher is dis-
played in increments of 0.1 A.
Display unit: A (Ampere)