Parameter
No.
Function name Data
Default
data
Unit
3004Hex-0FH
ex
Power Interruption Re-
start Mode Selection
0: Immediately trip (Free run stop)
1: Trip after a recovery from power failure (Free
run stop)
2: T
rip after decelerate-to-stop
3: Continue to run
4: Restart at the frequency selected by
(301FHex-35Hex)
6: Decelerate-to-stop (w/o trip)
1 -
3005Hex-02H
ex to
3005Hex-06H
ex,
3005Hex-63H
ex,
3005Hex-64H
ex
Input Terminal [DI1] to
[DI7] Function Selec-
tion
26: STM (Enable auto search for idling motor
speed at starting)
22: IL (Interlock)
- -
3008Hex-0AH
ex
Motor Starting Mode
Auto Search Function
Selection
0: Disable
1: Enable only at restart after momentary power
failure
2: Enable at normal start and restart after mo-
mentary power failure
0 -
3014Hex-44H
ex
Motor Starting Mode
Auto Search in Speed
Sensor less V
ector
Control
1
-
3008Hex-11H
ex
Allowable Time for
Power Interruption Re-
start
0.0 to 30.0
999: Auto judgment
32767 s
3008Hex-0EH
ex
Power Interruption Re-
start Wait T
ime
0.1 to 100.0 0.5 s
3008Hex-0FH
ex
Deceleration Setting
During Current Limit
for Restart Mode after
Power Interruption
0.00: Selected deceleration time
0.01 to 100.00
999: According to current limiter
32767 Hz/s
3008Hex-10H
ex
Continuous Running
Voltage Level
200 to 300 (200 V class series)
400 to 600 (400 V class series)
235
V
3008Hex-32H
ex
Auto Search Delay
Time 1 for Starting
Characteristic
0.0 to 10.0 0
s
3008Hex-2FH
ex
Auto Search Delay
Time 2 for Starting
Mode
0.1 to 100.0 1.0
s
3008Hex-5DH
ex
Continuous Running at
the Momentary Power
Failure P Proportional
Gain
0.000 to 10.000
999: Auto
32767 -
3008Hex-5EH
ex
Continuous Running at
the Momentary Power
Failure Integral Time
0.010 to 10.000
999: Auto
32767
s