EasyManua.ls Logo

Omron 3G3M1-A4110-ECT - Page 417

Omron 3G3M1-A4110-ECT
850 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Perform wiring with reference to the wiring example to meet the applicable safety standards. Be sure
to use both the safety input [SF1] and [SF2] terminals and configure a system that turns OFF both of
the [SF1] and [SF2] terminals when the safety function is activated.
If the inverter detects that either the [SF1] or [SF2] terminal is OFF, the safety function is activated and
the inverter shuts of
f the output.
The STO (Safe Torque Off) Performance Monitor (102: EDM) turns ON when the inverter detects
that both of the [SF1] and [SF2] terminal signals turn OFF and shuts off the output. If the EDM out-
put does not turn ON even when the inverter shuts off the output by the safety function, check the
[SF1] and [SF2] terminal input circuits and the EDM detection circuit.
The EN circuit failure detected (101: DECF) turns ON when an error occurs in the circuit that detects
that the SF terminal is OFF.
Parameter No. Function name Data
Default da-
ta
Unit
3005Hex-15Hex/
3005Hex-1CHex
Output Terminal [DO1] Function
Selection/Output Terminal
[ROA, ROB] Function Selection
101: DECF (EN circuit fail-
ure detected)
102: EDM (STO (Safe T
or-
que Off) Performance Mon-
itor)
- -
Wiring Example
Wiring example when EDM is enabled (for compliance with ISO13849-1 PL-e)
+24V
SF2
SF1
DIC
DOC
DO1
DO2
X
M
24V
EDM
3G3M1
System Configuration Example
To attain CAT.3, PL e/SIL3 as an overall system that uses the 3G3M1 Series, a PL e/SIL3 device must
at least be combined into the system.
8 Other Functions
8-63
M1 Series EtherCAT Type User’s Manual (I670)
8-6 Safety Function
8
8-6-3 STO Function by Safety Input Signal

Table of Contents

Related product manuals