PID Control Sleep
Timer for Process
Control
(300EHex-11Hex)
PID Control Restart Frequency after
Stopping for Process Control (300EHex-12Hex)
PID Control Sleep Frequency for
Process Control (300EHex-10Hex)
Time
Wakeup signal
“PID-STP”
The MV rises
again when
the pressure
(PV) drops.
RUN command
Feedback (PV)
Piping route
internal pressure
PID output (MV)
Output frequency
Acceleration time
setting
Deceleration time
setting
Starting
frequency
The pressure rises
when inverter operation
is resumed.
ON
ON
Command (SV)
The pressure starts dropping
by opening the faucet.
• PID Control Restart Delay Time after Stopping for Process Control (300EHex-19Hex)
The inverter restarts when both of the following conditions are satisfied.
1. The discharge pressure falls, the frequency reference value of the PID controller output rises, PID
Control Restart Frequency after Stopping for Process Control (300EHex-12Hex) is exceeded, and
PID Control Restart Delay Time after Stopping for Process Control (300EHex-19Hex) elapses.
2.
The difference between SV (command value) and PV (feedback value) becomes more than PID
Control Restart Feedback Deviation after Stopping for Process Control (300EHex-18Hex), and the
PID Control Restart Delay Time after Stopping for Process Control (300EHex-19Hex) elapses.
300EHex
-10Hex
[300EHex-18Hex ≠ 0] & [300EHex-19Hex ≠ 0]
Wakeup signal
“PID-STP”
Feedback PV(%)
Output frequency (Hz)
ON
ON
t
t
t
SV
PID output (MV)
300EHex-11Hex time elapsed
Not started
MV < 300EHex-10Hex
300EHex-19Hex
time elapsed
MV ≥ 300EHex-12Hex
SV-PV ≥ 300EHex-18Hex
Note 1
Note 1
Normal operation: SV-PV ≥ 300EHex-18Hex
Reverse operation: SV-PV ≤ 300EHex-18Hex
300EHex-
11Hex
300EHex-19Hex
300EHex-
18Hex
300EHex-12Hex
MV ≥ 300EHex-12Hex
[300EHex-18Hex = 0] & [300EHex-19Hex = 0]
(Factory default value) (Factory default value)
8 Other Functions
8-121
M1 Series EtherCAT Type User’s Manual (I670)
8-9 Other Operation Functions
8
8-9-13 PID Function