Motor speed
Magnetic flux
Rated
magnetic flux
ON
FW
Pre-excitation Timer (3008Hex-56Hex)
Controlling by Pre-excitation Command Terminal (32: EXITE)
Pre-excitation starts operating when the EXITE terminal is turned ON regardless of the setting of Pre-
excitation Timer (3008Hex-56Hex). After this, when the RUN command is input, pre-excitation opera-
tion ends, and acceleration starts. When the time until the RUN command is input is short, establish-
ment of magnetic flux sometimes does not arrive at a suf
ficient level. In this case, lengthen the time
until the RUN command is input.
Parameter No. Function name Data
Default da-
ta
Unit
3005Hex-02Hex to
3005Hex-06Hex,
3005Hex-63Hex,
3005Hex-64Hex
Input Terminal [DI1] to [DI7]
Function Selection
32: EXITE (Pre-excite) - -
Motor speed
Magnetic flux
ON
EXITE
ON
FW
Pre-excitation
Rated magnetic flux
The pre-excitation function is disabled in V/f control (including automatic torque boost and torque
vector). Substitute it with DC braking or starting frequency continuation.
Even when the motor is stopped by the pre-excitation operation, the voltage is output to the output
terminals [U], [V] and [W] of the inverter
.
8 Other Functions
8-136
M1 Series EtherCAT Type User’s Manual (I670)