Alarm
code
Alarm
subcode
Name Description  Check point and remedy reference
1B Hex
(0S)
0000 Hex
Excessive
speed protec-
tion
(1) Error in parame-
ter settings
Check 1st Motor Pole Number
(3007Hex-02Hex*) settings.
Set 3007Hex-02Hex* to match the mo-
tor used.
Check 1st Maximum Output Frequency
(3004Hex-04Hex*) settings.
Set 3004Hex-04Hex* to match the out-
put frequency
.
Check Speed Limit 1 in Forward
(3014Hex-21Hex) and Speed Limit 2 in Re-
verse (3014Hex-22Hex) settings.
Disable Speed Limit 1 in Forward
(3014Hex-21Hex) and Speed Limit 2 in
Reverse (3014Hex-22Hex).
Check Over Speed Detection Level
(3014Hex-24Hex) settings.
Set Over Speed Detection Level
(3014Hex-24Hex) to 120%.
(2) Insufficient speed
regulator gain
Check that the speed does not overshoot
during high-speed running.
Increase Speed Control 1 P Proportional
Gain (3014Hex-04Hex*).
  (In some cases, a review of filters and
integral time will be necessary
.)
(3) Noise superim-
posed on the PG sig-
nal
Check the PG signal input monitor
, and
check measures against noise (grounding
conditions, signal wiring/main circuit wiring
and installation methods, etc.).
Implement measures against noise.
(4) Output frequency
and motor rotation
speed exceeded 599
Hz
If using at near 590 Hz, check that the accel-
eration time is not short, there is no load var-
iation, and that the speed regulator Speed
Control 1 P Proportional Gain
(3014Hex-04Hex*) and Speed Control 1 I In-
tegral T
ime (3014Hex-05Hex*) are appropri-
ate.
Decrease the run frequency.
06 Hex
(during ac-
celeration)
(0U1)
07 Hex
(during de-
celeration)
(0U2)
08 Hex
(during con-
stant speed
operation)
(0U3)
(0Un)
0000 Hex Overvoltage
(1) The power supply
voltage exceeds the
inverter specification
range (three-phase
200 V and single-
phase 200 V: 420
VDC/three-phase
400 V
: 840 VDC)
Measure the input voltage.
Decrease the power supply voltage to
within the specified range.
If the power supply voltage is within the
specification range, this indicates an in-
verter fault. Replace the inverter.
(2) Surge in the input
power supply
When a phase advance capacitor is turned
ON/OFF or a thyristor converter operates on
the same power supply system, a transient
abnormal surge may occur in input voltage.
Set a DC reactor.
9 Troubleshooting
9-22
M1 Series EtherCAT Type User’s Manual (I670)