Loading...
Index
(hex)
Sub-
index
(hex)
Pa-
rame-
ter No.
Function name Monitor or data range
Default
data
Set-
ting
dur-
ing
RUN
Unit
PDO
map
3C C59 Input Terminal
[AI1] Analog In-
put Adjustment
Maximum Scale
V/f DTV
PG V/f PG DTV
SLV PGV
PM SLV PM PGV
-999.00 to 9,990.00
100 --- --- Possible
3D C60 Input Terminal
[AI1] Analog In-
put Adjustment
Minimum Scale
V/f DTV
PG V/f PG DTV
SLV PGV
PM SLV PM PGV
-999.00 to 9,990.00
0 --- --- Possible
5A C89 Set-point Factor
Numerator via
Communication
V/f DTV
PG V/f PG DTV
SLV PGV
PM SLV PM PGV
-32,768 to 32,767
1
--- Possible
5B C90 Set-point Factor
Denominator via
Communication
V/f DTV
PG V/f PG DTV
SLV PGV
PM SLV PM PGV
-32,768 to 32,767
1
--- Possible
A-4-8
P Group Parameter List (Motor 1 Parameters)
Index
(hex)
Sub-
index
(hex)
Pa-
rame-
ter No.
Function name Monitor or data range
Default
data
Set-
ting
dur-
ing
RUN
Unit
PDO
map
3007 02 P01 1st Motor Pole
Number
V/f DTV
PG V/f PG DTV
SLV PGV
PM SLV PM PGV
2 to 128
4 --- Poles Possible
03 P02 1st Motor Ca-
pacity
V/f DTV
PG V/f PG DTV
SLV PGV
PM SLV PM PGV
0.01 to 1,000
5.50 --- kW Possible
04 P03 1st Motor Rated
Current
V/f DTV
PG V/f PG DTV
SLV PGV
PM SLV PM PGV
0.00 to 500.0
21 --- A Possible
05 P04 1st Auto Tuning
Function Selec-
tion
V/f DTV
PG V/f PG DTV
SLV PGV
PM SLV PM PGV
0: Disable
1: Tune the motor parameters while
stopped
2: T
une the motor parameters while
rotating
4: Tune the PM motor magnetic pole
position offset while rotating
5: Tune the motor %R1 and %X
while stopped
0 --- --- Possible
Appendices
A-129
M1 Series EtherCAT Type User’s Manual (I670)
A-4 Lists of Manufacturer Specific Objects 2
(Inverter Parameters)
A
A-4-8 P Group Parameter List (Motor 1 Parameters)

Table of Contents

Related product manuals