Event name Mock Alarm Event code 68440000 hex
Meaning A Mock Alarm occurred.
Source EtherCAT Master Function Mod-
ule
Source details Slave Detection tim-
ing
Continuously
Error attrib-
utes
Level Minor fault Recovery Error reset Log category System log
Effects User program Continues. Operation Motor stops.
Indicators EtherCAT NET RUN EtherCAT NET ERR EtherCAT LINK/ACT
--- --- ---
System-de-
fined varia-
bles
Variable Data type Name
None None None
Cause and
correction
Assumed cause Correction Prevention
(1) Mock Alarm (3008-2E hex) is
set to 1.
Reset the alarm by executing
Reset (Refer to 6-8-1 Reset
Function on page
6-43).
Do not set
Mock Alarm
(3008-2E hex) to 1 except where
necessary.
Attached in-
formation
None
Precautions/
Remarks
None