5 Installation
5-28
CJ2 CPU Unit Hardware User’s Manual
z Wiring
Make sure that all Units are connected properly.
Do not remove the protective label from the top of the Unit until wiring has been completed.
This label prevents wire strands and other foreign matter from entering the Unit during wiring pro-
cedures.
Remove the label after wiring has been completed to allow air circulation needed for cooling.
Wire the Units so that they can be easily replaced.
Make sure that the I/O indicators are not covered by the wiring.
Do not place the wiring for I/O Units in the same duct or raceway as power lines. Inductive noise
can cause errors in operation.
Tighten the terminal screws to the torque of 0.5 N·m.
z Terminal Blocks
The I/O Units are equipped with removable terminal blocks. The lead wires do not have to be
removed from the terminal block to remove it from an I/O Unit.
After you complete wiring, check to see if the terminal block is securely locked.
OD211
0 123
4 5 6 7
8 9 10 11 12 13 14 15
OD211
01234567
8 9 10 11 12 13 14 15
After wiringDuring wiring
Remove the label.
17.5 mm
Screw (M3 screw with
self-raising pressure plate)
112DO
0123 4567
8 9 10 11 12 13 14 15
Terminal block lever
CJ-series Basic I/O Unit