EasyManua.ls Logo

Omron CJ2 CPU UNIT - Input Signal Width

Omron CJ2 CPU UNIT
424 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3-29
3 Nomenclature and Functions
CJ2 CPU Unit Hardware User’s Manual
3-6 CJ-series Basic I/O Units
3
3-6-1 Basic I/O Units with Terminal Blocks
z Application Precautions
Interrupt Input Units must be mounted in the locations described below.
When using a CJ2H-CPU6@-EIP CPU Unit, all Interrupt Input Units must be connected in any of the
four positions immediately to the right of the CPU Unit, i.e., slots 0 to 3 on the CPU Rack. When
using a CJ2H-CPU6@ CPU Unit or CJ2M-CPU@@ Unit, all Interrupt Input Units must be connected
in any of the five positions immediately to the right of the CPU Unit, i.e., slots 0 to 4 on the CPU
Rack. If an Interrupt Input Unit is connected in any other position on the CPU Rack or anywhere on
an Expansion Rack, and I/O setting error (fatal) will occur.
Example: CJ2H-CPU6@-EIP
The Interrupt Input Units must be connected in the slot ranges specified above even when the I/O
tables are edited using the CX-Programmer. If the Interrupt Input Units are not connected in the cor-
rect positions, an error will occur when the I/O tables are generated from the CX-Programmer.
A401.10 will turn ON to indicate an I/O setting error and A405.08 will turn ON to indicate that an Inter-
rupt Input Unit is in the wrong position.
Note Even if a Unit is physically in one of the correct positions, a Dummy Unit can be registered in the I/O tables,
causing a Unit to be defined in a position different from its physical position.
There are limits to the number of Interrupt Input Units that can be mounted. If these limits are
exceeded, a too many I/O points error (fatal error) will occur.
The input response time cannot be changed for the CJ1W-INT01, and the related portions of the
Basic I/O Unit input time constants in the PLC Setup, and the setting status in A200 to A259 will not
be valid.
z Input Signal Width
Input signals must meet the following conditions.
Unit ON time OFF time
CJ1W-INT01 0.05 ms min. 0.5 ms min.
0 1 2 3 4 5 6 7 8 9
Power
Supply
Unit
CPU
Unit
Connect here.
Cannot be used.
ON OFF

Table of Contents

Related product manuals