A-15
Appendices
CJ2 CPU Unit Hardware User’s Manual
A-1 Specifications of Basic I/O Units
App
A-1-2 Basic I/O Units
z CJ1W-IA201 AC Input Unit (200 VAC, 8 Points)
*1 The Input ON and OFF response times for Basic I/O Units can be set to 0 ms, 0.5 ms, 1 ms, 2 ms, 4 ms, 8 ms,
16 ms, or 32 ms in the PLC Setup. When the response times have been set to 0 ms, the ON response time will
be 10 ms maximum and the OFF response time will be 40 ms maximum due to internal element delays.
*2 Terminal numbers A0 to A8 and B0 to B8 are used in this manual, but they are not printed on the Unit.
Note Although 16 I/O bits (1 word) are allocated, only 8 of these can be used for external I/O. This Unit is also
treated as a 16-point I/O Unit in the I/O tables.
Name 8-point AC Input Unit with Terminal Block
Model CJ1W-IA201
Rated Input Voltage 200 to 240 VAC 50/60 Hz
Rated Input Voltage Range 170 to 264 VAC
Input Impedance 21 kΩ (50 Hz), 18 kΩ (60 Hz)
Input Current
9 mA typical (at 200 VAC, 50 Hz),
11 mA typical (at 200 VAC, 60 Hz)
ON Voltage/ON Current 120 VAC min./4 mA min.
OFF Voltage/OFF Current 40 VAC max./2 mA max.
ON Response Time
18.0 ms max. (PLC Setup default setting: 8 ms)
*1
OFF Response Time
48.0 ms max. (PLC Setup default setting: 8 ms)
*1
Number of Circuits 8 (8 points/common, 1 circuit)
Number of Simultaneously ON Points 100% (8 points/common) simultaneously ON
Insulation Resistance 20 MΩ between external terminals and the GR terminal (500 VDC)
Dielectric Strength
2,000 VAC between the external terminals and the GR terminal for
1 minute at a leakage current of 10 mA max.
Internal Current Consumption 80 mA max.
Weight 130 g max.
Accessories None
Circuit Configuration
Terminal Connections
COM
IN0
IN7
820 Ω 1 MΩ
0.15 µF
220 Ω
Input indicator
Internal circuits
to
Signal
name
IN0
IN1
IN2
IN3
IN5
IN6
IN7
B0
B1
B2
B3
B4
B5
B6
B7
B8
IN4
A0
A1
A2
A3
A4
A5
A6
A7
A8
COM
NC
NC
NC
NC
NC
NC
NC
NC
NC
200 to 240 VAC
Signal
name
Connec-
tor pin
*2