1-15
1 Overview
CJ2 CPU Unit Hardware User’s Manual
1-3 Specifications
1
1-3-2 Performance Specifications
*4 A960 to A1471 and A10000 to A11535 cannot be accessed by CPU Bus Units, Special I/O Units, PTs, and Support Soft-
ware that do not specifically support the CJ2 CPU Units.
*5 Bits in the EM Area can be addressed either by bit or by word. These bits cannot be addressed by CPU Bus Units, Spe-
cial I/O Units, PTs, and Support Software that do not specifically support the CJ2 CPU Units.
*6 EM banks D to 18 cannot be accessed by CPU Bus Units, Special I/O Units, PTs, and Support Software that do not spe-
cifically support the CJ2 CPU Units.
*7 With CJ2H CPU Units with unit version 1.2 or later, force-setting/resetting bits in the EM Area is possible either for banks
that have been specified for automatic address allocation or for banks specified for the EM Area force-set/reset function.
With CJ2M CPU Units, force-setting/resetting bits in the EM Area is possible only for banks specified for the EM Area
force-set/reset function.
Items
CJ2H- CJ2M-
CPU64
(-EIP)
CPU65
(-EIP)
CPU66
(-EIP)
CPU67
(-EIP)
CPU68
(-EIP)
CPU
11/31
CPU
12/32
CPU
13/33
CPU
14/34
CPU
15/35
Auxiliary Area Read-only: 31,744 bits (1,984 words)
• 7,168 bits (448 words): Words A0 to A447
• 24,576 bits (1,536 words): Words A10000 to A11535
*4
Read/write: 16,384 bits (1,024 words) in words A448 to A1471
*4
Temporary Area 16 bits: TR0 to TR15
Timer Area 4,096 timer numbers (T0000 to T4095 (separate from counters))
Counter Area 4,096 counter numbers (C0000 to C4095 (separate from timers))
DM Area
32k words
*5
• DM Area words for Special I/O Units: D20000 to D29599 (100 words × 96 Units)
• DM Area words for CPU Bus Units: D30000 to D31599 (100 words × 16 Units)
EM Area 32k words/bank × 25 banks max.: E00_00000 to
E18_32767 max.
*5, *6
32k words/bank × 4 banks max.: E00_00000 to
E3_32767 max.
*5
32K
words ×
4 banks
32K
words ×
4 banks
32K
words ×
10 banks
32K
words ×
15 banks
32K
words ×
25 banks
32K words × 1 bank 32K words × 4
banks
Banks for
which bits
can be
force-
set/reset
*7
Using EM
Area force-
setting/reset-
ting
Banks 0
to 3 hex
Banks 0
to 3 hex
Banks 0
to 9 hex
Banks 0
to E hex
Banks 0
to 18 hex
Bank 0 hex Banks 0 to 3 hex
Using auto-
matic
address allo-
cation speci-
fications
Bank 3
hex
Bank 3
hex
Banks 6
to 9 hex
Banks 7
to E hex
Banks 11
to 18 hex
---
Index Registers IR0 to IR15
These are special registers for storing PLC memory addresses for indirect addressing. (Index Registers can be set
so that they are unique in each task or so that they are shared by all tasks.)
Cyclic Task Flag Area 128 flags
Memory Card 128 MB, 256 MB, or 512 MB
Operating Modes PROGRAM Mode: Programs are not executed. Preparations can be executed prior to program execution in this
mode.
MONITOR Mode: Programs are executed, and some operations, such as online editing, and changes to present
values in I/O memory, are enabled in this mode.
RUN Mode: Programs are executed. This is the normal operating mode.
Execution Mode Normal Mode
Programming Languages Ladder Logic (LD)
Sequential Function Charts (SFC)
Structured Text (ST)
Instruction Lists (IL)
Function
Blocks
Maximum number of defini-
tions
2,048 256 2,048
Maximum number of
instances
2,048 256 2,048
FB Program Area --- 20K steps