5 Installation
5-48
CJ2 CPU Unit Hardware User’s Manual
z Wiring Methods
Observe the following points when wiring power supply and signal cables.
When routing signal cables with differing characteristics through the same duct, always keep them
separated.
As much as possible, avoid routing multiple power supply lines through the same duct. If it cannot
be avoided, then construct a partition between them in the duct and ground the partition.
To avoid overheating the conduits when using conduits for wiring, do not place wires for a single
circuit in separate conduits.
Partitioning Methods for Signal and Power Supply Cables
(a) (b)
(c) (d)
Signal cables
Signal cables
Signal cables
Power supply cables
Power supply cables
Partition
Signal
cables
(A)
Signal
cables (B)
Signal
cables
(C)
Power
supply
cables
Parallel Wiring (Single Phase)
Correct
Correct
Power supply
Incorrect
Power supply
Power supply
Load
Load
Load