EasyManua.ls Logo

Omron CJ2 CPU UNIT - CJ1 W-CIF11 RS-422 A Converter; DIP Switch Settings; Electric Specifications; RS-232 C Connector

Omron CJ2 CPU UNIT
424 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendices
A-114
CJ2 CPU Unit Hardware User’s Manual
CJ1W-CIF11 RS-422A Converter
The CJ1W-CIF11 RS-422A Converter is used to convert RS-232C to RS-422A/485.
It is connected directly to the RS-232C port on a CJ2 CPU Unit.
It is not isolated, so the maximum distance for RS-422A/485 is 50 m.
Appearance
Electric Specifications
RS-422A/485 Terminal Block
RS-232C Connector
* The hood will have the same electric potential as the connector hood where it is connected.
DIP Switch Settings
*1 Set both pins 2 and 3 to either ON (2-wire) or OFF (4-wire).
*2 To disable the echo-back function, set pin 5 to ON (RS control enabled).
*3 When connecting to a device on the N side in a 1: N connection with the 4-wire method, set pin 6 to ON (RS
control enabled).
Also, when connecting by the 2-wire method, set pin 6 to ON (RS control enabled).
Signal name
RDA
RDB+
SDA
SDB+
FG
Pin No.
Signal
name
1FG
2RD
3SD
4CS
5RS
6+5 V
7, 8 NC
9SG (0 V)
Hood NC*
Pin No. Setting ON OFF
1 Terminating resistance set-
ting
Connects terminating resistance on
both ends of the transmission path.
Disconnects terminating
resistance.
2
2-wire/4-wire setting
*1
2-wire 4-wire
3
2-wire/4-wire setting
*1
2-wire 4-wire
4 Not used. --- ---
5
RS control selection for RD
*2
RS control enabled RS control disabled (Data
always received.)
6
RS control selection for SD
*3
RS control enabled RS control disabled (Data
always sent.)
RDA RDB+ SDA SDB+ FG
RDA
RDB+
SDA
SDB+
FG
RS-232C port
+5V 6
7
8
SG (0 V) 9
1 FG
2 RD
3 SD
4 CS
5 RS
Connector pin