A-125
Appendices
CJ2 CPU Unit Hardware User’s Manual
A-4 Connecting to a Serial Port on the CPU Unit
App
A-4-2 Connection Examples
Note 1 The maximum cable length for an RS-232C connection is 15 m. RS-232C communications specifications,
however, do not cover transmissions at 19.2 Kbps. Refer to documentation of the device being connected
when using this baud rate.
2 The CP1W-CIF11 RS-422A/485 Option Board is not isolated. The maximum transmission distance is
therefore 50 m. If the distance exceeds 50 m, use the isolated CP1W-CIF12, or connect the isolated NT-
AL001 RS-422A Link Adapter to the RS-232C port on the CP1W-CIF01 RS-232C Option Board. If you use
one of these methods, the maximum total transmission distance will be 500 m.
3 The maximum cable length for connecting to the NT-AL001 is 2 m.
4 The maximum branch cable length is 10 m.
z Examples of 1:1 Connections to RS-232C Ports
Connecting to E5CK Temperature Controllers
Port
Connection
type
Diagram
RS-422A/485 1:1
RS-422A/485 1:N
NT-AL001
RS-422A/485
RS-422A/
485
RS-422A/485 I/F
RS-232C I/F
RS-232C
Terminating
resistance ON
+5 V required
RS-422A/485 I/F
RS-422A/485
RS-422A/485
B500-AL001
RS-232C
RS-232C
RS-232C
RS-422A/485
NT-AL001
RS-422A/485 I/F
RS-232C I/F
Terminating
resistance ON
+5 V required
Terminating
resistance ON
Terminating
resistance ON
Terminating
resistance ON
Terminating
resistance ON
Terminating
resistance ON
1
2
3
4
5
7
8
9
FG
SD
RD
RS
CS
DR
ER
SG
13
14
1
SD
RD
SG
Signal name
D-sub, 9-pin
connector (male)
Pin No.
Signal name
CPU Unit
RS-232C Option Board
RS-232C
shield
Example: E5CK (OMRON Temperature Controller)
RS-232C: Terminal block
Terminal