2-19
2 Basic System Configuration and Devices
CJ2 CPU Unit Hardware User’s Manual
2-1 Basic System Configuration
2
2-1-4 Configuration Units
Special I/O
Units
Temperature
Control Units
4 control loops, tem-
perature- resistance
thermometer inputs,
NPN outputs
CJ1W-TC101 20 words 200 words 0 to 94
(uses
words for
2 unit
numbers)
40
Units
0.25 --- 150 g max.
4 control loops, tem-
perature- resistance
thermometer inputs,
PNP outputs
CJ1W-TC102 20 words 200 words 0 to 94
(uses
words for
2 unit
numbers)
40
Units
0.25 --- 150 g max.
2 control loops, tem-
perature-resistance
thermometer inputs,
NPN outputs, heater
burnout detection
CJ1W-TC103 20 words 200 words 0 to 94
(uses
words for
2 unit
numbers)
40
Units
0.25 --- 150 g max.
2 control loops, tem-
perature-resistance
thermometer inputs,
PNP outputs, heater
burnout detection
CJ1W-TC104 20 words 200 words 0 to 94
(uses
words for
2 unit
numbers)
40
Units
0.25 --- 150 g max.
Position Con-
trol Units
1 axis, pulse output;
open collector output
CJ1W-NC113 10 words 100 words 0 to 95 40
Units
0.25 --- 100 g max.
2 axes, pulse outputs;
open collector outputs
CJ1W-NC213 10 words 100 words 0 to 95 40
Units
0.25 --- 100 g max.
CJ1W-
NC214
*1*2
18 words
*3
None 0 to 94
(uses
words for
2 unit
numbers)
5
Units/
Rack
0.27 --- 170 g max.
4 axes, pulse outputs;
open collector outputs
CJ1W-NC413 20 words 200 words 0 to 94
(uses
words for
2 unit
numbers)
40
Units
0.36 --- 150 g max.
CJ1W-
NC414
*1*2
18 words
*3
None 0 to 94
(uses
words for
2 unit
numbers)
5
Units/
Rack
0.31 --- 220 g max.
1 axis, pulse output;
line driver output
CJ1W-NC133 10 words 100 words 0 to 95 40
Units
0.25 --- 100 g max.
2 axes, pulse outputs;
line driver outputs
CJ1W-NC233 10 words 100 words 0 to 95 40
Units
0.25 --- 100 g max.
CJ1W-
NC234
*1*2
18 words
*3
None 0 to 94
(uses
words for
2 unit
numbers)
5
Units/
Rack
0.27 --- 170 g max.
4 axes, pulse outputs;
line driver outputs
CJ1W-NC433 20 words 200 words 0 to 94
(uses
words for
2 unit
numbers)
40
Units
0.36 --- 150 g max.
CJ1W-
NC434
*1*2
18 words
*3
None 0 to 94
(uses
words for
2 unit
numbers)
5
Units/
Rack
0.31 --- 220 g max.
Space Unit
*4
CJ1W-SP001 None None --- --- --- --- 50 g max.
Type Name Specifications Model
Number of
words allo-
cated
(CIO 2000 to
CIO 2959)
Number of
words allo-
cated
(D20000 to
D29599)
Unit No.
Num-
ber
of
moun
table
Units
Current con-
sumption (A)
Weight
5
VDC
24
VDC