Advanced Function Setting Level Section 5-10
• Set the soak time unit for the simple program function.
â– Related Parameters
Program start, Soak time remain (operation level): Page 184
Bank * soak time, Bank * wait band (bank setting level): Page 215
Program pattern (initial setting level): Page 229
This parameter sets whether the set point that triggers a deviation alarm dur-
ing SP ramp operation is to be the ramp SP or target SP.
• Set whether the set point that triggers a deviation alarm is the ramp SP or
target SP.
â– Related Parameters
Bank * SP ramp set value (bank setting level): Page 211
ST (initial setting level): Page 228
• When this parameter is set to ON, you can switch between a remote SP
and local SP (by specifying one or the other in the SP Mode parameter).
The Set Point During SP Ramp parameter is always enabled.
t-u Soak Time Unit
The Program Pattern parameter
must not be set to OFF.
Setting range Default
m: Minutes, h: Hours m
Function
Setting
See
See
alsp Alarm SP Selection
Alarm 1, 2, and 3 functions must be
assigned.
The SP Ramp Set Value parameter
must not be set to OFF.
The ST parameter must be set to
OFF.
The alarm type must be set to 1, 2, 3,
4, 5, 6, or 7.
Setting range Default
sp-m: Ramp SP, sp: SP sp-m
Function
Setting
See
See
rspu Remote SP Enable
The ST parameter must be set to
OFF.
Function