Section 4 Settings Required for Basic Control
4-30
Settings Required
for Basic Control
The procedure for switching to manual mode during control and
changing the MV is explained in the following.
When Auto / Manual is selected with the PF1 setting or PF2 setting
(Initially the PF1 setting is Auto / Manual.)
1. Hold down the key for Auto / Manual at least 1 second. The
MANU indicator lights up and the mode changes to manual.
To return to auto mode, hold down the
key at least 1 second. The
MANU indicator goes off and the mode changes to auto.
When Auto / Manual is not selected with either the PF1 setting or PF2 setting
1. Press the M key repeatedly to select "a-m: Auto / Manual".
2. Press the U key to switch to "manu: Manual". The MANU indicator lights
up and the mode changes to manual.
To resume control, follow the same procedure to switch back to "auto:
Auto". The MANU indicator goes off and the mode changes to auto.
PF
25.0
1
0.0
0.0
25.0
1
0.0
manu
PF
25.0
1
0.0
0.0
25.0
1
0.0
0.0
a-m
1
auto
a-m
1
manu
25.0
1
0.0
manu
Switching between auto and manual is also possible by
event input or communication.
For event input switching, see "5.7 Using event input" (P.5-
29). For communication switching, see "5.9 Using com-
munication functions" (P.5-34).
Hint

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5AR - MANUAL 2 and is the answer not in the manual?

Omron E5AR - MANUAL 2 Specifications

General IconGeneral
BrandOmron
ModelE5AR - MANUAL 2
CategoryController
LanguageEnglish

Related product manuals