Section 6 Communication (CompoWay/F)
6-28
Communication
(CompoWay/F)
■ Cancel latch
This command cancels alarm latch. The command is used when the
alarm latch function is in use.
This command can be used in both setting area 0 and setting area 1.
If AT is being run in the specified channel, an operation error will
result.
• To use this command, "Write via communication" must be enabled
using the "Write via communication" operation command.
Response codes: The above indicates a normal end. For the response
codes, see "6.7 Operation commands (Communication/CompoWay/
F)" (P.6-11).
■ SP mode
Use this command to select the SP mode (Local SP / Remote SP). The
command can be used when cascade control or remote SP is in use.
This command can be used in both setting area 0 and setting area 1.
• If AT is being run in the specified channel, an operation error will
result.
To use this command, "Write via communication" must be enabled
using the "Write via communication" operation command.
Related
information
Description
Ch Command
"00" 1 Cancel alarm latch
"10" 2 Cancel alarm latch
"20" 3 Cancel alarm latch
"30" 4 Cancel alarm latch
"F0" All Cancel alarm latch
Command
"30" "05"
SRC
"0C"
Instruction
code
Related
information
MRC
Response
"30" "05" "0000"
Response code
SRCMRC
Related
information
Description
Ch Command
"00"
1
Local SP
"01" Remote SP
"10"
2
Local SP
(Cascade open)
"11"
Remote SP
(Cascade closed)
Command
"30" "05"
SRC
"0D"
Instruction
code
Related
information
MRC