Section 8 Setting data
8-72
Setting data
8.16 Expansion control setting level (l.exc)
This level includes advanced control settings such as operation after power ON, PID set auto selection,
and position proportional settings.
Adjustment
level
Operation Level
L key Less
than 1 second
L key
1 second or
more
L key
3 seconds
or more
Adjustment 2
level
L key Less
than 1 second
PID setting
level
Bank setting
level
25.0
0.0
0.0
Control in progress
L key Less
than 1 second
L keyLess than 1 second
L key Less
than 1 second
L key Less
than 1 second
Approximation
setting
level
Control initial setting
level
Input initial setting
level
L key Less
than 1 second
Control initial setting
2 level
L key Less
than 1 second
Display adjustment
level
Alarm setting
level
L key Less
than 1 second
L key Less than 1 second
L key Less
than 1 second
L key Less
than 1 second
Communication
setting
level
Control stops.
Control stop
l. adj
l. ad2
l. bnk
l. pid
l. tec
l. 0
l. 1
l. 2
l. 3
l. 4
l. 5
L key
1 second
or more
Password input
set value (in general):
-169
(-169)
Special function
setting
level
l. adf
Expansion control
setting
level
L key Less
than 1 second
l. exc
Power on
pidh
off
cont
0.50
M
M
M
M
M
sptr
p-on
alfa
pVtr
off
0.
mani
at-g
M
M
1.0
lcma
M
20.0
P-ON: Operation at power ON
CONT/STOP/MANU
PIDH:
PID set
automatic
selection
hysteresis
0.10 - 99.99
CJC.1: Input 1
Cold junction compensation
OFF/ON
CJC.4: Input 4
Cold junction
compensation
OFF/ON
ALFA: α
0.00 - 1.00
PVTR: PV tracking
OFF/ON
SPTR: SP tracking
OFF/ON
MANI:
Manual MV initial value
-5.0 - 105.0 (standard control)∗1
AT-G:AT calculated gain
0.1 - 10.0
LCMA:
Limit cycle MV amplitude
5.0 - 50.0
tate
M
10.0
TAT E:
Tentative A.T. execute judgment deviation
0.0 - 100.0
*1 Heating/cooling control
0.0
l.exc
pV
M
pidi
PIDI:
PID set automatic selection
data PV/DV
p-db
0.0
P-DB: PV dead band
0 - 99999
M
M
orlm
0
ORLM:
MV change rate limit mode
Mode 0:0 / Mode 1:1
M
at-h
0.
M
AT-H: AT hysteresis
0.1 - 9.9
rbmp
off
RBMP: Bumpless at Run
Disable: OFF / Enable: ON
pmec
M
off
PMEC:
Operation at potentiometer input error
Stop: OFF / Continue: ON
dost
M
off
DOST:
Disturbance overshoot adjustment function
OFF/ON
M
M
cjc.1
cjc.4
on
on
mant
hold
MANT: Manual output mothod
HOLD/INIT
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
Expansion Control Setting Level
65
2