Section 6 Communication (CompoWay/F)
6-12
Communication
(CompoWay/F)
FINS-mini response text
Response codes
Data name Explanation
MRC/SRC FINS-mini command text appears here.
Response code Result of execution of the command.
Response
code
Error name Explanation
"1001"
Command length
too long
The command is too long.
"1002"
Command length
too short
The command is too short.
"1100"
Parameter error Operation code or related information is
not correct.
"2203" Operation error
Unable to execute because write via
communication is disabled.
Unable to execute operation command.
For more information, see correspond-
ing operation command explanation in
"6.9 Commands and responses (Com-
munication/CompoWay/F)".
Unit error, unit change, display unit error,
internal non-volatile memory error
"0000" Normal end
Response
"30" "05"
Response code
(MRES/SRES)
SRCMRC
22 4