Section 8 Setting data
8-34
Setting data
● Related setting data
"Straight-line approximation 1 enable", "Straight-line approximation 2
enable" (Control initial setting 2 level) (P.8-51)
Use these settings to set values for broken-line approximation 1.
• Set values for broken-line approximation. Up to 20 points can be
specified for one broken line approximation. Use normalized data for
the values.
• If Input n
≥ Input n + 1, the setting of point "n + 1" will not be
effective.
● Related information
"5.1 Input adjustment functions
■
Broken-line approximation" (P.5-6)
● Related setting data
"Broken-line approximation 1 enable" (Control initial setting 2 level)
(P.8-51)
Setting
Setting data
Setting range
Units
Default value
Straight-line approximation
∗
Input 1
-1.999 to 9.999
− 0.000
Straight-line approximation
∗
Input 2
-1.999 to 9.999
− 1.000
Straight-line approximation
∗
Output 1
-1.999 to 9.999
− 0.000
Straight-line approximation
∗
Output 2
-1.999 to 9.999
− 1.000
Reference
Reference
Broken-line approximation 1 Input 1 to
Broken-line approximation 1 Input 20
Broken-line approximation 1 Output 1 to
Broken-line approximation 1 Output 20
fi01.1 to fi20.1
fo01.1 to fo20.1
Broken-line approximation ∗
is enabled
l.tec
Function
Input 2
6-point broken-line approximation characteristics
P2
Output 2
Input 3 Argument 1 (Input data)
P3
P4
P6
P5
Output 3
P5 disabled because
Input 5 ≤ Input 4
Operation result
Input 1
P1
P7 to 20
(Disabled)
Output 1
Setting
Setting data
Setting range Units
Default value
Broken-line approximation
∗
Input 1 to
Broken-line approximation
∗
Input 20
-1.999 to 9.999
−
0.000
Broken-line approximation
∗
Output 1 to
Broken-line approximation
∗
Output 20
-1.999 to 9.999
−
0.000
Reference
Reference