Cause Possible Solution
The contactor on the inrush prevention circuit
is damaged.
Cycle power to the drive. Check if the fault reoccurs.
Replace the drive if the fault continues to occur.
Check monitor U4-06 for the performance life of the inrush prevention circuit.
Replace the drive if U4-06 exceeds 90%.