EasyManuals Logo

Omron J1000 User Manual

Omron J1000
232 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #195 background imageLoading...
Page #195 background image
C.6 Drive Operations by MEMOBUS/Modbus
The drive operations that can be performed by MEMOBUS/Modbus communication depend on drive parameter settings.
This section explains the functions that can be used and related parameter settings.
u
Observing the Drive Operation
A
PLC can perform the following actions with MEMOBUS/Modbus communications at any time regardless of parameter
settings (except H5-).
Observe drive status and drive control terminal status from a PLC.
Read and write parameters.
Set and reset faults.
Set multi-function inputs. Inputs settings from the input terminals S and from MEMOBUS/Modbus communications
are both linked by an OR operation.
u
Controlling the Drive
To
start and stop the drive or set the frequency reference using MEMOBUS/Modbus communications, an external reference
must be selected and the parameters listed below must be adjusted accordingly.
Table C.1 Setting Parameters for Drive Control from MEMOBUS/Modbus
Parameter Name Required Setting
b1-01 Frequency Reference Selection 2
b1-02 Run Command Selection 2
Refer to b1-01: Frequency Reference Selection on page 72 and Refer to b1-02: Run Command Selection on page 73
for details on external reference parameter selections.
C.6 Drive Operations by MEMOBUS/Modbus
SIEP C710606 33A OYMC AC Drive – J1000 User Manual
193
C
MEMOBUS/Modbus
Communications

Table of Contents

Other manuals for Omron J1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron J1000 and is the answer not in the manual?

Omron J1000 Specifications

General IconGeneral
BrandOmron
ModelJ1000
CategoryInverter
LanguageEnglish

Related product manuals