Command Reference: Function Blocks Section 6-5
6-5-2 Function Block: Restart
Diagram
Default Connections
General Description
The Output Enable signal will turn ON if the Reset signal is correctly input
while the input condition to the Restart function block is ON.
This function block can be used to prevent the machine from automatically
restarting, e.g., when the power to the NE1A-series Controller is turned ON,
when the operating mode is changed (from IDLE Mode to RUN Mode), or
when a signal from a safety input device turns ON.
Functionally, the Reset function block and the Restart function block are
equivalent.
Conditions for Output Enable Turning ON
The Monitored Input and all enabled optional inputs must be ON.
And the Reset signal must be input correctly.
Conditions for Static Release Turning ON
The Monitored Input and all enabled optional inputs must be ON.
Conditions for Restart Required Indication Turning ON
If the following condition is met, the Restart Required Indication will become a
1-Hz pulse output.
The Monitored Input and all enabled optional inputs must be ON.
And Output Enable must be OFF.
If the Reset Signal is set to Low-High-Low, the Reset Required Indication will
turn ON when the next condition is met.
The Restart signal must be ON.
Set Parameters
The Reset Signal can be set in NE1A-series Controllers with unit version 1.0
or later.
Number of Inputs Setting
The number of inputs can be increased on the In/Out Setting Tab Page in the
function block property dialog box.
Output EnableReset
Monitored Input
Parameter Setting range
Default setting
Reset Signal Low-High-Low
Rising Edge
Low-High-Low
Parameter Setting range Default setting
Number of inputs 2 to 8 (Optional Input Settings) 2