Initial Setting Section 4-1
4-1-2 Software Settings
DeviceNet Communications Disable (Standalone) Setting
When DeviceNet Communications are disabled, the NE1A-series Controller
stops all DeviceNet communications and operates as a Standalone Control-
ler. The default is to have DeviceNet communications enabled (normal mode).
Make the setting from the Network Configurator. After the setting has been
made, a reset command will be sent from the Network Configurator to the
NE1A-series Controller to enable the setting.
IMPORTANT
• When DeviceNet communications are disabled, connect the NE1A-series
Controller to the Network Configurator via the USB connection.
• When DeviceNet communications are disabled, operation using the Net-
work Configurator can be performed via a USB connection.
Setting Description
Enabled (Normal Mode) DeviceNet communications enabled.
Disabled (Standalone Mode) DeviceNet communications disabled. The SNC will
operate as a Standalone Controller. "nd” will be displayed on