EasyManua.ls Logo

Omron NE1A Series - Operating Mode Changes; Operating Mode Setting at Startup

Omron NE1A Series
258 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
185
NE1A-series Controller Operating Modes Section 8-1
8-1-4 Operating Mode Setting at Startup
The user can select the NE1A-series Controller’s operating mode from the fol-
lowing two modes at startup, after the normal completion of configuration.
IMPORTANT When the power supply is interrupted in IDLE Mode, the NE1A-series Control-
ler will not start in RUN Mode at the next startup even though Automatic Exe-
cution Mode is set and the configuration is locked. Make sure to turn OFF the
power supply in RUN Mode.
8-1-5 Operating Mode Changes
NE1A-series Controller operating modes can be changed using the Network
Configurator.
A password may be required to change the operating mode.
IDLE Mode RUN Mode
RUN Mode IDLE Mode
Operating mode
on startup
Description
Normal Mode The NE1A-series Controller starts in IDLE Mode after configuration has been
completed. To switch to RUN Mode, use the Network Configurator to change the
mode at every startup.
Automatic
Execution Mode
When this mode is selected and the following operations are performed, the
NE1A-series Controller starts up in RUN Mode thereafter.
Configuration lock
Power supply interruptions after switching to RUN Mode.
IDLE RUNCONFIGURING
Configuring
Download completed normally.
Mode change
Mode change
Configuring

Table of Contents

Related product manuals