Nomenclature and Functions Section 2-1
2-1-6 Input/Output Terminals and Internal Connections
NE1A-SCPU01(-V1)
Terminal name Description
V0 Power supply terminal for internal circuits
The two V0 terminals are connected internally.
G0 Power supply terminal for internal circuits
The two G0 terminals are connected internally.
V1 Power supply terminal for external input devices and test outputs
G1 Power supply terminal for external input devices and test outputs
V2 Power supply terminal for external output devices
G2 Power supply terminal for external output devices
IN0 to IN15 Safety input terminals
T0 to T3 Test output terminals used to connect with safety inputs IN0 to IN15. Each
test output terminal outputs a different test pulse pattern. Terminal T3 also
supports a current monitoring function for the output signal, for example, for a
muting lamp.
OUT0 to OUT7 Safety output terminals