Command Reference: Function Blocks Section 6-5
General Description
The Routing function block routes one input signal to a maximum of eight out-
put signals. It is used to output a signal to more than one output tag.
Optional Output Settings
The number of outputs can be increased on the In/Out Setting Tab Page in the
function block property dialog box.
Maximum Number of Outputs for a Routing Logic Function
Truth Table
Truth Table for Routing Evaluation
0: OFF, 1: ON
6-5-12 Function Block: Muting
Diagram
Default Connections
General Description
This function can be used only in NE1A-series Controllers with unit version
1.0 or later.
The Muting function block temporarily disables the light-interruption signal
(AOPD input) in a light curtain while the muting signal is being detected. While
the muting function is operating, a detection object can be removed from the
light curtain’s detection zone without stopping machine operation.
Parameter Setting range Default setting
Number of outputs 1 to 8 1
Input 1 Output
1
Output
2
Output
3
Output
4
Output
5
Output
6
Output
7
Output
8
0
0 0 0 0 0 0 0 0
1 1 1 1 1 1 1 1 1
AOPD Input1 (NC)
AOPD Input2 (NC)
Muting Signal11
Muting Signal12
Output Enabl
e
Muting Status