Connection Status Tables Section 10-8
10-8-2 Connection Status for DST1 Series
Status Countermeasure
00:0001 Normal communications The Safety I/O connection status is normal.
01:0001 Safety I/O Connection
Timeout
The Safety I/O connection has timed out. Check the following items.
Do all nodes have the same baud rate?
Is the cable length correct (trunk lines and branch lines)?
Is the cable disconnected or slack?
Is the terminating resistance only on both ends of the main line?
Is there a lot of noise?
Is the network bandwidth allocation suitable?
01:0105 Configuration Owner Error The Safety Slave was configurated from a configuration tool or Safety
Master at a different node address last time. Reset the Safety Slave to the
default settings and download the device parameters again.
Refer to 5-1-2 Setting Safety Connection Parameters in the DeviceNet
Safety System Configuration Manual (Z905) for information on configura-
tion owners.
01:0106 Output connection Owner
Error
The Safety Slave established output safety I/o connections with a Safety
Master at a different node address last time.
Reset the Safety Slave to the default settings and download the device
parameters again.
Refer to 5-1-2 Setting Safety Connection Parameters in the DeviceNet
Safety System Configuration Manual (Z905) for information on output con-
nection owners.
01:0110 Device Not Configurated The Safety Slave has not been configurated. Download the device param-
eters to the Safety Slave.
01:0113 No. of Connections Error The setting for the number of safety I/O connections exceeds the upper
limit supported by the Safety Slave. Adjust the Safety Connection setting
for the relevant Safety Master.
01:0114 Vendor ID or Program
Code Error
The device data (vendor ID or product code) for the device on the Configu-
rator and the device used in the actual system does not match.
Use Safety Slave Verification (Device
Parameter
Verify) to check
that the device in the system and the device registered to the Safety Mas-
ter match.
If they do match, delete then re-register the connections registered to the
Safety Master.
01:0115 Device Type Error The device data (device type) for the device on the Configurator and the
device used in the actual system does not match.
Use Safety Slave Verification (Device
Parameter
Verify) to check
that the device in the system and the device registered to the Safety Mas-
ter match.
If they do match, delete then re-register the connections registered to the
Safety Master.
01:0116 Revision Error The device data (revision) for the device on the Configurator and the
device used in the actual system does not match.
Use Safety Slave Verification (Device
Parameter
Verify) to check
that the device in the system and the device registered to the Safety Mas-
ter match.
If they do match, delete then re-register the connections registered to the
Safety Master.