Command Reference: Function Blocks Section 6-5
Truth Tables
Setting: Single Channel
0: OFF, 1: ON
Setting: Dual Channel Equivalent
0: OFF, 1: ON
Setting: Dual Channel Complementary
0: OFF, 1: ON
Error Handling and Error Resetting
Input 1
(NC)
Output
Enable
0
0
1 1
Input 1
(NC)
Input 2
(NC)
Output
Enable
000
010
100
111
Input 1
(NC)
Input 2
(NO)
Output
Enable
00
0
010
101
110
Error Behavior for error detection Resetting the error
condition Output
Enable
Fault
Present
Error output condition
Discrepancy
error
OFF
(safety
state)
ON Discrepancy
Error output: ON
Remove the cause of the error
and then do the following:
1. Make the inputs inactive
and then active again.
2. Or change the NE1A-series
Controller’s operating mode
to IDLE Mode and then
back to RUN Mode.