73
Safety Master Function Section 4-4
Resetting a Connection Stopped due to a Communications Error
When I/O communications have stopped in a connection due to a connection
timeout, I/O communications can be restarted in the stopped connection by
turning ON the Communications Reset Flag from the logic program or send-
ing a Communications Restart command from the Network Configurator. If the
Controller communications mode is set to stop all connections after a commu-
nications error, communications cannot be restarted in a specified stopped
connection. In this case, restart communications in all connections.
1. Restarting I/O Communications from the Network Configurator
After connecting online with the Network Configurator, select the Safety
Master, right-click to display the popup menu, and select Monitor to dis-
play the Device Monitor Window. The following window will appear when
the safety connection is selected.
Communications can be restarted in a connection where an error occurred
(evident from the connection status) by selecting that connection and clicking
the Resume Button. If the Resume All Button is clicked, I/O communications
will restart in all Slaves with which communications were stopped.
2. Restarting I/O Communications from the Logic Program
When the safety connection is set, the following logic program output tags
will be displayed for the connection.
Communications restart tags
for specific connections
Communications restart tag
for all connections