7 Tag Data Link Functions
7-50
NJ-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
Differences Found in the Device Type
Click the OK Button or the Close Button.
Use the following procedure to compare the device parameters for the devices selected in the Network
Configuration Pane with those of the devices connected on the EtherNet/IP network. The IP addresses,
device types, and device parameters are compared.
1
Connect the Network Configurator online.
2
Click the icon of the built-in EtherNet/IP port to verify. To select multiple nodes, press and hold
the Shift Key while you select additional icons. (In the following example, 2 nodes are selected:
192.168.250.1 and 192.168.250.2.)
Right-click the icon to display the pop-up menu and select Parameter
Verify.
3
The following dialog box is displayed.
Click the Yes Button or the No Button.
Verifying the Device Parameters