2-7
2 Installing Ethernet Networks
NJ-series CPU Unit Built-in EtherNet/IP Port Users Manual (W506)
2-2 Network Installation
2
2-2-3 Precautions
Do not lay the twisted-pair cable in locations subject to excessive dirt and dust or to oil mist or other
contaminants.
Do not ground the Ethernet switch in the same location as a drive-system component, such as an
inverter.
Always use a dedicated power supply for the Ethernet switchs power supply. Do not use the same
power supply for other equipment, such as an I/O power supply, motor power supply, or control power
supply.
Before installation, check the Ethernet switchs environmental resistance specifications, and use a
Ethernet switch that is appropriate for the ambient conditions. Contact the Ethernet switch manufac-
turer for details on Ethernet switchs environmental resistance specifications.
Connect two Ethernet switches to each other as follows:
Connect an MDI port to an MDI-X port with a straight cable.
Connect two MDI ports or two MDI-X ports with a cross cable.
Note It is very difficult to distinguish cross cables and straight cables by appearance. Incorrect cables will cause
communications to fail. We recommend cascade connections with straight cables whenever possible.
Some Ethernet switches can automatically distinguish between MDI and MDI-X. When this kind of
Ethernet switch is used, straight cable can be used between Ethernet switches.
Precautions for Correct UsePrecautions for Correct Use
Adjust the built-in EtherNet/IP ports link settings to match the communications settings of the
connected Ethernet switch. If the settings do not match, the link will be unstable and prevent nor-
mal communications. The following table shows the allowed settings for each Ethernet switch
communications mode. (Auto-Nego: Auto negotiation, Full: Full duplex, Half: Half duplex)
Best = Recommended; OK = Allowed; --- = Not allowed.
Ethernet Switch Installation Environment Precautions
Ethernet Switch Connection Methods
Ethernet switch
Built-in EtherNet/IP port
Auto-
Nego
10 Mbps (fixed) 100 Mbps (fixed)
Full Half Full Half
Auto-Nego Best --- OK --- OK
10 Mbps (fixed) Full --- OK --- --- ---
Half OK --- OK --- ---
100 Mbps (fixed) Full --- --- --- Best ---
Half OK --- --- --- OK
Cross cable
Straight cable
Ethernet
switch
Ethernet switch
MDI port
MDI-X port (cross)
Ethernet
switch
Ethernet
switch