2-17SectionDevice Monitor Function
277
Error RemedyProbable cause
Remove trouble execution
fails.
(when clearing an error from
error log screen)
The cause of the PC error
has not been eliminated.
Eliminate the cause of the error that you are trying to
clear. For details, refer to the PC’s operation manual.
Connection failed.
(when starting the Device
Monitor function)
The Device Monitor function
was called when the PT was
not connected to a PC that
supports Device Monitor.
Check the model of the PC that is connected. (Refer to
2-17-1 Compatible Systems for a table of PCs that
support the Device Monitor function.)
Set Comm. Method to NT
Link (1:1 or 1:N)
(when the Device Monitor
menu is being displayed)
The communications protocol
set at the PT is not 1:1 NT
Link or 1:N NT Link.
Check the memory switches (fourth screen) and set the
connected PC’s serial port protocol to 1:1 NT Link or
1:N NT Link. Set the same protocol in the PC.
(Serial port reception error
screen being displayed)
The connecting cable is
disconnected or faulty.
Verify the connection between the PT and PC. For
details, refer to section 7 of the Setup Manual.

Table of Contents

Other manuals for Omron NT21

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron NT21 and is the answer not in the manual?

Omron NT21 Specifications

General IconGeneral
BrandOmron
ModelNT21
CategoryTouch terminals
LanguageEnglish

Related product manuals