A - 45
Appendices
NX-series Analog I/O Units User’s Manual for Analog Input Units and Analog Output Units (W522)
A-3 List of NX Objects
A
A-3-2 Analog Input Units
*1. The default value and data range for Number of Entries are as follows.
*2. The setting range of Chîš… Input Moving Average Time depends on the model. The input moving average time data range
for each type is as follows.
Index
(hex)
Subindex
(hex)
Object name
Default
value
Data range Unit
Data
type
Acc
ess
I/O
allo-
cat-
ion
Data
attri-
bute
5004 --- Input Moving Average
Time
--- --- --- --- --- --- ---
00 Number of Entries
*1 *1
--- USINT RO Not
pos-
sible
---
01 Ch1 Input Moving Average
Time
0
*2
μsUINT RWNot
pos-
sible
Y
02 Ch2 Input Moving Average
Time
0UINTRWNot
pos-
sible
Y
03 Ch3 Input Moving Average
Time
0UINTRWNot
pos-
sible
Y
04 Ch4 Input Moving Average
Time
0UINTRWNot
pos-
sible
Y
05 Ch5 Input Moving Average
Time
0UINTRWNot
pos-
sible
Y
06 Ch6 Input Moving Average
Time
0UINTRWNot
pos-
sible
Y
07 Ch7 Input Moving Average
Time
0UINTRWNot
pos-
sible
Y
08 Ch8 Input Moving Average
Time
0UINTRWNot
pos-
sible
Y
NX Units Default value Data range
NX-AD2203/AD2204/AD2208/
AD2603/AD2604/AD2608
22
NX-AD3203/AD3204/AD3208/
AD3603/AD3604/AD3608
44
NX-AD4203/AD4204/AD4208/
AD4603/AD4604/AD4608
88
Other models 0 0
NX Units Data range
NX-AD2203/AD2204/AD2603/
AD2604/AD3203/AD3204/
AD3603/AD3604/AD4203/
AD4204/AD4603/AD4604
0 to 32000
NX-AD2208/AD2608/AD3208/
AD3608/AD4208/AD4608
0 to 640